Incident update

Cause not yet confirmed

In this training case, start with fitting and threading the new roll: the manual requires the upper holder to be secured, the adhesive side correctly oriented and the change confirmed on the panel. The timing favors this branch, but neither a specific fault nor a sensor or wiring inspection has been confirmed.

Do not replace the sensor without evidence

An alternative is the I94B2 unwinding sensor, its bracket or cable. The Strema 5997 history records sensor replacement, bracket tightening and a torn cable repair. Another possibility is a missing prestretch command, which also depends on the dancer and sequence step.

First safe step

First record the exact alarm text and current HMI step. Secure the machine against unexpected movement before inspection; then compare film routing with chapter 6.1 and check roll retention, the bracket, cable -W94B2 and connector. No check is considered completed yet. Fault: Film does not unwind / film tearApr 8, 2026

Evidence and missing information

PLCs

Distinguish unwinding failure from a signal fault

The current export maps I94B1 to %I36.4, I94B2 to %I36.5 and I94B3 to %I36.6. The film-unwinding/tearing alarm network has an 8 s timer, but uses I94B2 OR I94B3 levels rather than explicit missing-edge monitoring. Without live states, the historical interpretation cannot be accepted as a confirmed diagnosis. Fault: Film does not unwind / film tearing13. 2. 2026

Database evidence

Replacement sensor only after confirming the fault
What was investigated

Snowflake Warehouse: find the IFM IFS204 / IFB3004BBPKG/M/US inventory sensor or material 1014026986, normalizing leading zeros. Also search complete identifiers within longer manufacturer, supplier and material-description values, without plant restrictions. Return identifiers, name, part number, inventory, unit, plant, warehouse and location. This is a conditional replacement; the fault is unconfirmed.

Evidence gaps (5)

  • The actual alarm, sequence step and observations of the roll, rollers and dancer are missing.
  • Inspection findings and live input, command and drive-state values are unavailable; a specific failed component cannot be identified.
  • The discrepancy between the historical missing-pulse interpretation and the PLC level condition remains unresolved.
  • Searching Snowflake Warehouse maintenance orders for Strema or 5997 without date or plant restrictions returned no records; this does not prove there were no faults.
  • Compatibility of the IFS204 inventory candidates and the material marked IFC204 is unconfirmed.