Maintenance record: film problem

Details

Source Type
Manual import
Created by
Daniel Whitmore
daniel.whitmore@demo.edmundai.com
Event DateApr 8, 2026, 5:30 PM
CreatedOct 23, 2026, 2:43 PM

Description

Fault description The machine reported a film-related fault. Inspection of the film carriage found a loose sensor bracket and a broken cable. This caused an incorrect or missing sensor signal for film tension or pulses.

Solution

Maintenance journal entry — Strema 5997 wrapper (film carriage). Event date: 2026-04-08. Equipment: Strema SAD16B wrapper, machine 5997. Location: film carriage (ASi Slave 16B — film sensors). Cause: the sensor bracket loosened mechanically due to vibration or impact, overloading and breaking the sensor cable. Work performed: secured the machine against unintended movement; identified the damaged sensor and cable on the loose bracket; replaced the sensor with IFM IFS204 / IFB3004BBPKG/M/US, order number 16110; refastened the bracket and checked the M12 connector and cable routing. Functional test: checked the diagnostic input and performed a wrapping test cycle. Result: the fault was removed and the machine ran without errors. Prevention: check bracket fastenings, cable wear or tension and strain relief when a film fault occurs. Material used: one IFM IFS204 sensor.